H-series

21 people are viewing this right now

Description

High quality control component

It strictly complies with CE and IEC standards and is empowered with advanced electric control technology and able to work under a power source of 380V±20%. In addition, it is installed with a power supply protection module, enabling it to make a selection of protective value in a range of 380V±50%. When voltage goes beyond the selected range, it will automatically protect the unit. While the voltage becomes normal, it will automatically restart the unit.

Evaporator

An efficient evaporator made from quality material with advanced professional technology and featuring large heat exchange area and realization of higher sensible heat factor of precision air conditioning unit.

Expansion

Expansion valve adopts advanced thermal expansion valves with strong reliability and stability and can precisely control the supply of refrigerant. In order to achieve the reduction of energy consumption for refrigerant equipment, we employ advanced electronic expansion valves in high-performance precision air conditioning units to realize less energy consumption.

Humidifier

An internationally advanced electrode steam humidification system under which the amount of humidification and water inflow and outflow are all controlled by computer, the auto cleaning program for the humidifier cylinder ensure normal humidification efficiency of the cylinder.

Cabinet

With unique frame design and black framework demonstrating consummate production technology, professional design and elegant appearance, the cabinet guarantee the safety of unit under any transport condition and operating environment.

Filter

Air filer under G4 standard which is metallic bracket, filtering the dust and particulate effectively by air circulation, then purifying the air environment of telecom room.

Scroll Compressor

The core power of unit is from Copeland hermetic scroll compressor that guarantees the high efficiency, low noise and long life of the unit.

Indoor blower fan

A blow fan adopts direct drive centrifugal fan with backward curved blades, the range of static pressure can be adjusted from 0 to 400pa, realizing the continuous operation of 365 days*24 hours, 10 years’ average life. The high-performance unit employ energy-saving EC fan controlled by 0-10V signal,DC driven and stepiess speed regulation, which is more excellent than traditional fan in energy-saving field.

Heater

An electric heater with perfect overheat protection function and ionization resistance, able to meet environmental requirements of the small heat-load machine rooms for base stations in cold arctic-alpine area.

Condenser

With an enclosure of anti-corrosion alloy that ensures service life and appearance of the condenser, an external rotor axial flow fan that is elaborately designed and able to satisfy the environment protection requirements on noise,and a fan speed regulator that controls the rotating speed under different temperature and ensure sound operating effect and energy saving.

 

Model:HADR/HAUR

0201

0251

0261

0271

0301

0351

0401

0451

Cooling capacity(1)

kw

21.2

23.2

26.8

27.3

31.5

35.6

41.2

44

Air flow

m3/h

6530

7050

7280

8500

9000

10000

11000

13000

EER

3.72

3.60

3.60

3.75

3.71

3.71

3.71

3.68

SHR

0.98

0.98

0.92

0.98

0.99

0.98

0.97

0.95

Compressor
Type

Scroll

Capacity

kw

5.2

5.5

5.9

6.2

7.4

8.3

9.3

10.1

Quantity

nr

1

1

1

1

1

1

1

1

Finned coil evaporator
Frontal surface

m2

0.8

0.8

0.8

1.4

1.4

1.4

1.7

1.7

Geometry

mm

25*21.65
Type of fans

  Hydrophilic

Fin pitch

mm

1.8
Fan section
Type

Centrifugal fan

Quantity

nr

1

1

1

1

1

1

2

2

Absorbed current

A

2.5

2.5

2.8

3.2

3.5

4.1

4.4

4.9

Absorbed power

W

1050

1100

1200

1300

1320

2000

2150

2400

AESP Max Speed(2)

Pa

360

360

360

380

380

355

355

355

Air filter
Efficiency

EU4

Overall surface

m2

5.8

5.8

5.8

6.5

6.5

6.5

7.8

7.8

Fire resistance class

1

Electrical heaters
Total heating capacity

kw

5

5

5

5

5

8

8

8

Quantity

nr

2

2

2

2

2

2

2

2

Material

PTC

Humidifier
Capacity

Kg/h

8-13

8-13

8-13

8-13

8-13

8-13

8-13

8-13

Absorbed power

kw

6

6

6

6

6

6

6

6

Dimension&Weight
Height

mm

1998

1998

1998

1998

1998

1998

1998

1998

Length

mm

1000

1000

1000

1000

1000

1000

1750

1750

Depth

mm

795

795

795

795

795

795

795

795

Weight

kg

375

385

393

450

490

590

595

610

Sound level
Sound pressure level(3)

dB(A)

52

53

53

55

56.5

58

60

60

 

Model:HADR/HAUR

0272

0322

0362

0422

0452

0512

0522

0652

0692

0752

0852

0912

1022

Cooling capacity(1)

kw

26.9

31.9

35.9

41.9

44.3

50.5

54.4

61.4

68.7

76.2

85.5

90.8

102

Air flow

m3/h

8000

9000

10000

11500

12950

13500

16000

17500

18000

21000

23500

23500

24200

EER

3.60

3.65

3.66

3.61

3.63

3.72

3.72

3.65

3.61

3.61

3.61

3.65

3.62

SHR

0.95

0.96

0.93

0.95

0.93

0.93

0.95

0.96

0.95

0.93

0.95

0.94

0.93

Compressor
Type

Scroll

Capacity

kw

6.0

7.0

8.2

9.2

10.0

11.0

11.2

13.6

15.8

17.6

18.6

19.6

22.4

Quantity

nr

2

2

2

2

2

2

2

2

2

2

2

2

2

Finned coil evaporator
Frontal surface

m2

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

2.8

2.8

2.8

2.8

Geometry

mm

25*21.65
Type of fins

Hydrophilic

Fin pitch

mm

1.8
Fan section
Type

Centrifugal fan

Quantity

nr

2

2

2

2

2

2

2

2

2

3

3

3

3

Absorbed current

A

4.3

4.3

4.3

4.4

4.4

4.4

5

5.2

5.2

6.5

16.5

16.5

16.5

Absorbed power

W

1600

1600

1800

1800

2000

2000

3000

3300

3900

3900

5400

6300

6300

AESP Max Speed(2)

Pa

380

380

380

355

355

355

380

380

380

360

400

400

400

Air filter
Efficiency

EU4

Overall surface

m2

7.8

7.8

7.8

7.8

7.8

7.8

7.8

7.8

7.8

13.5

13.5

13.5

13.5

Fire resistance class

1

Electrical heaters
Total heating capacity

kw

5

5

5

10

10

10

10

10

10

12

12

24

24

Quantity

nr

2

2

2

3

3

3

3

3

3

2

2

4

4

Material

PTC

Humidifier
Capacity

Kg/h

8-13

8-13

8-13

8-13

8-13

8-13

8-13

8-13

8-13

8-13

8-13

8-13

8-13

Absorbed power

kw

6

6

6

6

6

6

6

6

6

6

6

6

6

Dimension&Weight
Height

mm

1998

1998

1998

1998

1998

1998

1998

1998

1998

1998

1998

1998

1998

Length

mm

1750

1750

1750

1750

1750

1750

1750

1750

1750

2500

2500

2500

2500

Depth

mm

795

795

795

795

795

795

795

795

795

795

795

795

795

Weight

kg

565

580

590

605

615

615

620

625

625

979

985

992

1015

Sound level
Sound pressure level(3)

Db(A)

56

58

59

62

62

63

64

65

65

65

65

65

66

Select the fields to be shown. Others will be hidden. Drag and drop to rearrange the order.
  • Image
  • Rating
  • Description
  • Add to enquiry
Click outside to hide the comparison bar
Compare